# 2025-07-08 — datacenter-group wg. USVs und Diesel-Generator
## Datum
## 👥 Teilnehmer
- [Florian.Hammer@datacenter-group.com](mailto:Florian.Hammer@datacenter-group.com)
- Philip, Stefan
## 📒 Thema
> <br>
## 📖 Notizen
- usvs nicht mehr im Schrank
- Batterielaufzeit über das Schott Frischluft
- Batteriepacks außerhalb vom Schrank
- Wartung Batterien ist möglich
- Be und Entlüftung der Batterie nicht normgerexhr
- Diesel Fest installiert über Dachböden 
- Mobil unklar 
- Tür geht nicht weit genug auf
- 67cm Tür Nadelöhr Heizungskeller 
- Schrank steht 2 cm zu nah an der wand für USV Schublade → muss aus dem Schrank raus
- Be und entlüftung benötigt 
- Knallgas im alten serverraum - Thema?
- It last ohne Reserve 
- ggf 30% vom Max Wert aus Datenblatt 
- Alternativer aufstellort 
- 15 / 16 kw geschätzt 
- Neha
-